CC-Link IE Field Master/Slave

CC-Link IE Field brings 1 Gigabit speed for cyclic, acyclic and transient data transmission to RJ45 and Cat 5e cabling infrastructure. Create mixtures of line and star topology, and maintain control over up to 120 controller or remote I/O stations simultaneously on the same network.

Model Number

LJ71GF11-T2

Stocked Item

S

Certification

UL • cUL • CE

Network Common Memory

32k bytes

Transient Transmission Capacity

2048 bytes

Ethernet

Communication Speed

1Gbps

Connection Cable

An Ethernet cable that meets the 1000BASE-T standard (Category 5e or higher, shielded RJ45)

Maximum Station-to-Station Distance

100m max. (Compliant with ANSI/TIA/EIA-568-B (Category 5e))

Total Distance

Line topology: 12000m (when connected to 1 master station and 120 slave stations) Star topology: Depends on the system configuration

Number of Cascade Connections

Up to 20

Transmission Path

Star, Line, Mixed Star & Line, and Ring

Number of Connected Stations in One Network

Master Station

1 station

Local Station

120 stations (Local station or Remote I/O) (*1)

Maximum Number of Networks

239

Communication Method

Token passing method

Number of Occupied I/O Points

32 points (I/O assignment: Intelligent 32 points)

Internal Current Consumption (5VDC) (A)

0.89

Weight (kg)

0.27

Dimensions (W x H x D) mm

45 x 90 x 95

Note 1: For CC-Link IE Field Remote I/O stations, refer to the LJ72GF15-T2 CC-Link IE Field Slave Head station.

 

CC-Link IE Field Slave Head Station

In place of an L Series CPU, CC-Link IE Field Slave Head Stations can be used to provide remote control over Digital I/O, Analog, Motion, High-Speed Counter, Serial Communication, and CC-Link Master/Local Station modules via CC-Link IE Field.

Model Number

LJ72GF15-T2 (*1)

Stocked Item

S

Certification

UL • cUL • CE

Transmission Speed

1Gbps

Network Topology

Star, Line, Mixed Star & Line, and Ring

Communication Method

Deterministic (token passing)

Maximum Number of Mountable Modules

10 (120 when using extension and branch modules)

Communication Port

CC-Link IE field network port x 2, USB port (Mini-B terminal) x 1

RAS Function

Network event logging, unit error logging, testing, monitoring, and error history preservation function

Connection Cable

Ethernet cable (category 5 or higher)

Dimensions (W x H x D) mm

50 x 90 x 95

Note 1: CC-Link IE Field network requires CC-Link IE Field Master module.

 

CC-Link IE Field Head Station Supported L Series I/O Modules

Product

Model Number

Description

Stocked Item

Power Supply (REQUIRED)

L61P

L Series PSU, 100-240VAC, 5VDC 5A

S

L63P

L Series PSU, 24VDC, 5VDC 5A

S

Digital Inputs

LX10

L Series 16pt 100-240VAC Input, Screw Terminals

S

LX28

L Series 8pt 100-240VAC Input, Screw Terminals

S

LX40C6

L Series 16pt 24VDC Input, Sink/Source, Screw Terminals

S

LX41C4

L Series 32pt 24VDC Input, Sink/Source, 40 pin Connector

S

LX42C4

L Series 64pt 24VDC Input, Sink/Source, 40 pin Connector x2

S

Digital Outputs

LY10R2

L Series 16pt Relay Output, Screw Terminals

S

LY20S6

L Series 16pt 264VAC Triac Input, Screw Terminals

S

LY40NT5P

L Series 16pt 12-24VDC Sink Transistor Output, Screw Terminals

S

LY40PT5P

L Series 16pt 12-24VDC Source Transistor Output, Screw Terminals

S

LY41NT1P

L Series 32pt 12-24VDC Sink Transistor Output, 40 pin Connector

S

LY41PT1P

L Series 32pt 12-24VDC Source Transistor Output, 40 pin Connector

S

LY42NT1P

L Series 64pt 12-24VDC Sink Transistor Output, 40 pin Connector x2

S

LY42PT1P

L Series 64pt 12-24VDC Source Transistor Output, 40 pin Connector x2

S

Analog I/O

L60AD4

L Series 4ch Analog Input, Voltage/Current, Scaling, Error History

S

L60DA4

L Series 4ch Analog Output, Voltage/Current, Scaling, Error History

S

Temperature Control

L60TCTT4

L Series 4ch Temperature Control (Thermocouple)

S

L60TCRT4

L Series 4ch Temperature Control (PT100)

S

L60TCTT4BW

L Series 4ch Temperature Control (Thermocouple) with Wire Break

S

L60TCRT4BW

L Series 4ch Temperature Control (PT100) with Wire Break

S

High-Speed Counter

LD62

L Series 2ch High-Speed Counter, 5/12/24VDC Input, 200KHz

S

LD62D

L Series 2ch High-Speed Counter, Differential Driver Input, 500KHz

S

Positioning Module (*1)

LD75D4

L Series 4-axis Pulse Positioning, 200Kpps, Positioning Data

S

LD75P4

L Series 4-axis Differential Driver Positioning, 4Mpps, Positioning Data

S

Motion Module (*1)

LD77MH4

L Series 4-axis SSCNETIII Motion, Positioning Data Table, Cam, Encoder, Phase Compensation

S

LD77MH16

L Series 16-axis SSCNETIII Motion, Position Data Table, Cam, Encoder, Phase Compensation

S

CC-Link Interface

LJ61BT11

L Series CC-Link Ver.2 Master/Local Station

S

Serial Communication

LJ71C24

L Series 2ch Serial Communication, RS-232, RS-422/485

S

LJ71C24-R2

L Series 2ch Serial Communication, RS-232 x2

S

End-Cover (Accessory) (*2)

L6EC-ET

L Series End-Cover with Error Output Relay

S

 
Note: See L Series PLC section for more information. CC-Link IE Field Remote I/O Head Station must be setup using GX Works2 version 1.31H or later. See Software section for more information.
1. Requires LJ72GF15-T2 with Serial Number starting with 12081 or higher.
2. The LJ72GF15-T2 Head Station is supplied with a standard End-Cover without an Error Output Relay.

 

CC-Link Master/Local Station

Additional CC-Link Master/Local Stations can be added on and configured in GX Works2.

Model Number

LJ61BT11

Stocked Item

S

Certification

UL • cUL • CE

Transmission Speed

156kbps/625kbps/2.5Mbps/5Mbps/10Mbps

Maximum Overall Cable Distance (Maximum Transmission Distance)

1.2 km (without repeater, varies according to the transmission speed.)

Maximum Number of Connected Stations (Master Station)

64

Number of Occupied Stations (Local Station)

1 to 4 stations (The number of stations can be switched using the GX Works2 parameter setting.)

Maximum Number of Link Points Per System (*1)

Remote I/O (RX, RY)

2048 points

Remote Register (RWw)

256 points (master station remote device station/local station/intelligent device station/standby master station)

Remote Register (RWr)

256 points (remote device station/local station/intelligent device station/standby master station master station)

Number of Link Points Per Station (*1)

Remote I/O (RX, RY)

32 points (local station is 30 points)

Remote Register (RWw)

4 points (master station remote device station/local station/intelligent device station/standby master station)

Remote Register (RWr)

4 points (remote device station/local station/intelligent device station/standby master station master station)

Transmission Path

Bus (RS-485)

RAS Function

Automatic return function; Slave station cut-off function;
Error detection via link special relay/register

Connection Cable

CC-Link dedicated cables compatible with Ver.1.10

I/O Device Points Occupied

32 points (I/O assignment: 32 points for intelligent function module)

5VDC Internal Current Consumption

0.46A

Weight (kg)

0.15

Dimensions (W x H x D) mm

28.5 x 90 x 118

Note 1: Indicates the number of link points for Remote net Ver.1 mode.

 

IO Link Master

Model Number

ME1IOL6-L

Stocked Item

-

Number of Ports

6

Port Configuration

IO-Link, Digital output (SIO mode), Digital input (SIO mode), Disabled

IO-Link Mode

Rated Voltage

24 VDC

Rated Output Current (C/Q)

15 mA

Rated Sensor/Actuator Supply Current (L+)

200 mA

SIO Mode

Digital Input

Input Type

Sink

Rated Voltage

24 VDC

Internal Pull-Down Current (C/Q)

5 mA

Input Filter (HW and SW)

200 μs

Digital Output

Rated Voltage

24 VDC

Rated Output Current (C/Q)

200 mA Max. current per port (sum of C and L+): 215 mA

Rated Sensor/Actuator Supply Current (L+)

Output Type

Push-pull

Port Disabled

Communication Line (C/Q)

Switched OFF

Sensor/Actuator Supply Line Switched OFF (L+)

Protection Functions

Communication Line (C/Q)

Over-current, over-load and short-circuit

Sensor/Actuator Supply Line (L+)

Insulation Method

Between the I/O Terminals and PLC Power Supply

Photocoupler isolation

Between Channels

No isolation

Dielectric Withstand Voltage

Between I/O terminals and programmable controller power supply:
500 V ACrms for 1 minute

Insulation Resistance

Between I/O terminals and programmable controller power supply:
500 VDC 10 MΩ or more

Number of I/O Occupied Points

32 points (I/O assignment: Intelligent 32 points)

External Wiring Connection System

18-points terminal block

Cable Specification

Cable Type

Unshielded cable

Maximum Length

20 m

Applicable Wire Size

0.3 to 0.75mm²

Overall Loop Resistance

6 Ω

Effective Line Capacitance

3 nF

Applicable Solderless Terminals

R1.25-3 (Solderless terminals with sleeves cannot be used)

External Supply Power

Voltage

24 VDC (+20%, -15%); ripple, spike within 500mVP-P In order to keep the specified IO-Link output voltage levels (L+ line) the external supply voltage must be higher than 22 VDC

Current (A)

The sum current on the L- lines must not exceed 1.7

Inrush Current

8 A within 230 μs

Internal Current Consumption (5 VDC) (A)

0.06

Online Module Change

Not supported

Weight (kg)

0.18

 

CC-Link/LT Master Module

Model Number

LJ61CL12

Stocked Item

-

Certification

UL • cUL • CE

Transmission Speed

156kbps/625kbps/2.5Mbps

Network Topology

T-branch

Communication Method

Deterministic (CRC)

Number of Connectable Modules

64

Number of Occupied I/O Points

16 points (I/O assignment: 1024points for intelligent function module)

5VDC Internal Current Consumption

0.16A

Weight (kg)

0.12

Dimensions (W x H x D) mm

28.5 x 90 x 95