High-speed counter modules can be added on and configured in GX Works2 using built-in utilities.

Model Number

LD62 (DC Input)

LD62D (Differential Input)

Stocked Item

S

S

Certifications

UL • cUL • CE

Number of Channels

2ch

Counting Speed Switch Setting

10kpulse/s, 100kpulse/s, 200kpulse/s

10kpulse/s, 100kpulse/s, 200kpulse/s, 500kpulse/s

Count Input Signal

Phase

1-phase input (multiple of 1/2), CW/CCW, 2-phase input (multiple of 1/2/4)

Signal Level

5/12/24VDC 2 to 5mA

EIA Standard RS-422-A differential type line driver level (Equivalent with AM26LS31)

Counter

Maximum Counting Speed

200kpulse/s

500kpulse/s

Counting Range

Binary with 32-bit code (-2147483648 to 2147483647)

Type

UP/DOWN preset counter (+ ring counter function)

Minimum Count Pulse Width (Duty Ratio 50%)

10kpulse/s

50μs

100kpulse/s

5μs

200kpulse/s

2.5μs

10kpulse/s

50μs

100kpulse/s

5μs

200kpulse/s

2.5μs

500kpulse/s

1μs

Minimum Phase Differential for 2-Phase Input

10kpulse/s

25μs

100kpulse/s

2.5μs

200kpulse/s

1.25μs

10kpulse/s

25μs

100kpulse/s

2.5μs

200kpulse/s

1.25μs

500kpulse/s

0.5μs

Comparison Output

Comparison Range

Binary with 32-bit code (-2147483648 to 2147483647)

Comparison Result

Set value < Count value; Set value = Count value; Set value > Count value

External Input

Preset

5/12/24VDC 2 to 5mA

5/12/24VDC 2 to 5mA (Differential type line drivers conforming to EIA standard RS-422-A are also applicable.)

Function Start

Minimum Input Response Time

OFF – ON

Function start: 0.5ms

ON – OFF

Function start: 1ms

External Output

Comparison Output

2 points/channel

Output Voltage/Current

12 to 24VDC 0.5A

Output Response Time

OFF – ON

0.1ms or less (rated load, resistive load)

ON – OFF

I/O Device Points Occupied

16 points (I/O assignment: 16 points for intelligent function module)

External Connections

40-pin connector

5VDC Internal Current Consumption (A)

0.31

0.36

Weight (kg)

0.13

Dimensions (W x D x H) mm

28.5 x 90 x 95