Temperature Controller modules
|
Item |
R60TCTRT2TT2 |
R60TCRT4 |
R60TCTRT2TT2BW |
R60TCRT4BW |
||
|
Stocked Item |
S |
S |
S |
S |
||
|
Certification |
UL • cUL • CE |
|||||
|
Control Output |
Transistor output |
|||||
|
Number of Temperature Input Points |
4 channels/module |
|||||
|
Applicable Thermocouple/Platinum Resistance Thermometer |
R, K, J, T, S, B, E, N, U, L, PLII, W5Re/W26Re |
Pt100, JPt100 |
R, K, J, T, S, B, E, N, U, L, PLII, W5Re/W26Re |
Pt100, JPt100 |
||
|
Accuracy |
Indication Accuracy |
Ambient Temperature: 25±5°C |
Full scale x (±0.3%) |
|||
|
Ambient Temperature: |
Full scale x (±0.7%) |
|||||
|
Cold Junction Temperature Compensation Accuracy (Ambient Temperature: 0 to 55°C) |
Temperature Process Value: -100°C or Higher |
Within ±1.0°C |
- |
Within ±1.0°C |
- |
|
|
Temperature Process Value: -150 to -100°C |
Within ±2.0°C |
Within ±2.0°C |
||||
|
Temperature Process Value: -200 to -150°C |
Within ±3.0°C |
Within ±3.0°C |
||||
|
Sampling Cycle |
Switchable between 250ms/4 channels and 500ms/4 channels |
|||||
|
Control Output Cycle |
0.5 to 100.0s |
|||||
|
Input Impedance |
1MΩ |
|||||
|
Input Filter |
0 to 100s (0: Input filter OFF) |
|||||
|
Sensor Correction Value Setting |
When the R mode is used (-(full scale of input range)) to full scale of input range) When the Q compatible function is used -50.00 to 50.00% |
|||||
|
Operation at a Sensor Input Disconnection |
Upscale processing |
|||||
|
Temperature Control Method |
PID ON/OFF pulse or two position control |
|||||
|
PID Constants Range |
PID Constants Setting |
Setting by auto tuning is available. |
||||
|
Proportional Band (P) |
When the R mode is used 0 (0.0) to full scale of input range (depending on the decimal point position) |
|||||
|
Integral Time (I) |
0 to 3600s (Set 0 for P control and PD control.) |
|||||
|
Derivative Time (D) |
0 to 3600s (Set 0 for P control and PI control.) |
|||||
|
Set Value Setting Range |
Within the temperature range set in the thermocouple/platinum resistance thermometer to be used |
|||||
|
Dead Band Setting Range |
When the R mode is used 0 (0.0) to full scale of input range (depending on the decimal point position) When the Q compatible function is used 0.1 to 10.0% |
|||||
|
Transistor Output |
Output Signal |
ON/OFF pulse |
||||
|
Rated Load Voltage |
10 to 30VDC |
|||||
|
Maximum Load Current |
0.1A/point, 0.4A/common |
|||||
|
Maximum Inrush Current |
0.4A, 10ms |
|||||
|
Leakage Current at OFF |
0.1mA or lower |
|||||
|
Maximum Voltage Drop at ON |
1.0VDC (TYP) 0.1A, 2.5VDC (MAX) 0.1A |
|||||
|
Response Time |
OFF–ON: 2 ms or less, ON–OFF: 2 ms or less |
|||||
|
Heater Disconnection Detection Specifications |
Current Sensor |
- |
The following current sensors of URD, Ltd: CTL-12-S36-10 (0.0 to 100.0A), CTL-12-S56-10 (0.0 to 100.0A), CTL-6-P-H (0.00 to 20.00A), CTL-6-S-H (0.00 to 20.00A), CTL-12L-8 (0.0 to 100.0A) |
|||
|
Input Accuracy |
Full Scale x (±1.0%) |
|||||
|
Number of Alert Delay |
3 to 255 times |
|||||
|
Number of Occupied I/O Points |
16 Points |
32 Points |
||||
|
External Connection System |
18-point terminal block |
18-point terminal block x2 |
||||
|
Applicable Solderless Terminal |
R1.25-3 (The solderless terminal with an insulation sleeve cannot be used) |
|||||
|
Internal Current Consumption |
0.28A |
0.31A |
||||
|
Weight (kg) |
0.22 |
0.34 |
||||
|
Base Unit Slots Occupied |
1 slot |
2 slots |
||||